Fire Collar for Plastic Pipe Penetration Seals
Floor waste collars help prevent the passage of fire and smoke through openings in compartment floors in the event of a fire. For installation of collars on permanent formwork and in thin floor slabs (<150mm) always contact Promat. These collars are available in various models and the type used depends on the certification required for the building.
PROMASEAL® Floor Waste Collars (Patent Pending) are designed to provide fire resistance where floor wastes penetrate wet areas. The collars have been tested for cast-in floor applications with the pipe fitting within the collar and when tested to AS1530: Part 4 and AS4072: Part 1 achieved an FRL of -/240/240.
The FWC100 collar is suitable for 50, 80 & 100mm uPVC, 100mm HDPE and 100mm Rehau Raupiano pipe.
Minimum Slab depth is 150mm.