PROMASTOP® UniCollar®

ADVANTAGES

  • Single box solution for multiple pipe sizes and types
  • Fixings and Clips included in the box
  • Wall, Ceiling and Slab approvals
  • Tested for a wide variety of pipe including uPVC, HDPE, Raupiano, d-Blue, Triplus and many others
  • Approved to protect cable bunches and insulated metal pipes.

Fire Resistant Collar for Plastic Pipes Penetration Seals

PROMASTOP® UniCollar® is an intumescent device designed to maintain the integrity of the fire resistant elements through which various plastic pipes pass. It is suitable for retrofit installation in various floors and walls similar to that in which it has been tested. In the event of a fire, the intumescent material in the PROMASTOP® UniCollar® rapidly expands, closing off the plastic pipe or combustible insulation and forming an insulating barrier.

PROMASTOP® UniCollar® is currently tested with many new and existing types of plastic using uPVC as a benchmark.

PROMASTOP® Unicollar® is packed in individual boxes each containing 2250mm length of collar (or 150 segments) and fixing accessories are included. The collar is designed so that it can be cut and snapped in modules of 15mm. For a guide to the approximate number of collar sizes per strip, please refer to the usage guide table.

Applications

Usage guide
< #Back#

USAGE GUIDE

Inside diameter (I/D) mm 43 50 55 63 69 75 83 90 110 114 125 140 160 200**
inches 1.25 1.5 - 2 - 2.5 - 3 - 4 - 5 6 -
Segments per collar
(UL listing if featured)
15 17 18 20
(19)
21 22 24 25 29 30 33 36 40
(42)
49
Approximate number of collars per box 10 8.5 8 7.5 7 6.5 6 6 5 5 4.5 4 3.5
(3.75)
3
Number of brackets per collar for floor application 2 2 2 2 2 3 3 3 3 3 4 5 5 5
Number of brackets per collar for wall application 2* 2* 2* 2* 2* 3 3 3 3 3 3 5 5 5

These figures based on uPVC and HDPE pipes. Contact Promat for other pipe types

*Three brackets are recommended for framed walls if framing is not available to be fixed on.

**200mm only approved for HDPE Pipes

PROMASTOP® UniCollar® are manufactured under a quality management system certified in accordance with ISO 9001: 2008. The production unit has passed the site audit of ISO 14001 and all manufacturing processes are in accordance with the environmental standards of ISO 14001: 2004 and the safety standards of AS 4801: 2001.

USAGE GUIDE

Inside diameter (I/D) mm 43 50 55 63 69 75 83 90 110 114 125 140 160 200**
inches 1.25 1.5 - 2 - 2.5 - 3 - 4 - 5 6 -
Segments per collar
(UL listing if featured)
15 17 18 20
(19)
21 22 24 25 29 30 33 36 40
(42)
49
Approximate number of collars per box 10 8.5 8 7.5 7 6.5 6 6 5 5 4.5 4 3.5
(3.75)
3
Number of brackets per collar for floor application 2 2 2 2 2 3 3 3 3 3 4 5 5 5
Number of brackets per collar for wall application 2* 2* 2* 2* 2* 3 3 3 3 3 3 5 5 5

These figures based on uPVC and HDPE pipes. Contact Promat for other pipe types

*Three brackets are recommended for framed walls if framing is not available to be fixed on.

**200mm only approved for HDPE Pipes

PROMASTOP® UniCollar® are manufactured under a quality management system certified in accordance with ISO 9001: 2008. The production unit has passed the site audit of ISO 14001 and all manufacturing processes are in accordance with the environmental standards of ISO 14001: 2004 and the safety standards of AS 4801: 2001.

Floor Waste
< #Back#
The PROMASTOP® UniCollar® is not approved for and should not be used in Floor Waste Applications. Where protection of floor wastes is required, refer to the PROMASEAL® Floor Waste Retrofit Collar.
The PROMASTOP® UniCollar® is not approved for and should not be used in Floor Waste Applications. Where protection of floor wastes is required, refer to the PROMASEAL® Floor Waste Retrofit Collar.
Health & Safety
< #Back#

HEALTH & SAFETY

No special precautions are required. For more information please check the material safety data sheet:

WASTE DISPOSAL

Handle as construction industry waste and dispose of in compliance with all local and national regulations in the appropriate and approved manner.

HEALTH & SAFETY

No special precautions are required. For more information please check the material safety data sheet:

WASTE DISPOSAL

Handle as construction industry waste and dispose of in compliance with all local and national regulations in the appropriate and approved manner.