PROMASEAL® IBS™

ADVANTAGES

  • Up to 4 hours fire resistance
  • Easy to use
  • Quick to install
  • Allow for pipe movement
  • Approvals for control joints as well as penetration seals for metal pipes, cables and cable trays
  • Coloured for ease of identification

Fire Resistant Flexible Foam Strip

PROMASEAL® IBS™ is a fire resistant, flexible foam strip which, when placed in joints and around service penetrations in floors and walls, will maintain the fire resistance of the separating element. In most instances the addition of PROMASEAL®-A Acrylic Sealant is necessary. On some occasions a non fire resistant sealant can be applied.

PROMASEAL® IBS™ is a factory made product and can be easily verified as being installed in the correct manner.

PROMASEAL® IBS™ generally is used in lieu of a fire resistant sealant where the specifying authority or certifying body is concerned that the correct depths of sealant or the correct type sealant may not be applied by the contractor.

PROMASEAL® IBS™ accommodates movement in building services, e.g. the expansion or contraction of metal pipes, while maintaining the integrity of the penetration. It can be used for external wall joints in conjunction with an exterior grade sealant.

PROMASEAL® IBS™ is not designed for use in control joints that are designed to accommodate high or ongoing movement.

Dimensions
< #Back#

Dimensions

Colour: Green

 
Bag Quantities
16mm – 150m
22mm – 100m
29mm – 60m
38mm – 30m
50x20mm – 50m
100x10mm – 50m

Dimensions

Colour: Green

 
Bag Quantities
16mm – 150m
22mm – 100m
29mm – 60m
38mm – 30m
50x20mm – 50m
100x10mm – 50m

Performance
< #Back#

PERFORMANCE

Configuration Maximum joint width (mm) Nominal dimension of IBS™ (mm) Minimum depth of non fire resistant sealant (mm) Maximum fire resistance
System to non fire exposed side only 18
30
35
54
65
22
38
38
60
80
9 (optional)*
12 (optional)*
12
18
20
-/240/120
-/240/120
-/240/120
-/180/120
-/180/120
System to fire exposed side only 18
18
35
54
65
22
22
38
60
80
9 (optional)**
12
12
18
20
-/240/240
-/240/240
-/240/240
-/240/240
-/240/240
System to mid depth of element 18
30
50
22
38
60
Not required
Not required
5
-/240/120
-/180/90
-/240/120

* If sealant is not used in this application the fire resistance achieved will be -/180/90. For joints up to 30mm wide it is possible to install a 10mm thick PROMASEAL® IBS™ into the joint on the element’s side exposed to fire without a sealant coating.

** If sealant is not used in this application the fire resistance achieved will be -/240/180. For joints up to 30mm wide it is possible to install a 12mm thick PROMASEAL® IBS™ from the element’s side unexposed to fire without a sealant coating.

The non fire resistant sealant consists of acrylic, silicone or polyurethane based materials. To install PROMASEAL® IBS™, compress and insert into the joints. For gaps up to 30mm, it is possible to install the PROMASEAL® IBS™ in the centre of the depth/thickness of the floor or wall without a sealant fill. The fire reistance achieved depends on the existing fire resistance level of the building element in which the PROMASEAL® IBS™ is installed.

PERFORMANCE

Configuration Maximum joint width (mm) Nominal dimension of IBS™ (mm) Minimum depth of non fire resistant sealant (mm) Maximum fire resistance
System to non fire exposed side only 18
30
35
54
65
22
38
38
60
80
9 (optional)*
12 (optional)*
12
18
20
-/240/120
-/240/120
-/240/120
-/180/120
-/180/120
System to fire exposed side only 18
18
35
54
65
22
22
38
60
80
9 (optional)**
12
12
18
20
-/240/240
-/240/240
-/240/240
-/240/240
-/240/240
System to mid depth of element 18
30
50
22
38
60
Not required
Not required
5
-/240/120
-/180/90
-/240/120

* If sealant is not used in this application the fire resistance achieved will be -/180/90. For joints up to 30mm wide it is possible to install a 10mm thick PROMASEAL® IBS™ into the joint on the element’s side exposed to fire without a sealant coating.

** If sealant is not used in this application the fire resistance achieved will be -/240/180. For joints up to 30mm wide it is possible to install a 12mm thick PROMASEAL® IBS™ from the element’s side unexposed to fire without a sealant coating.

The non fire resistant sealant consists of acrylic, silicone or polyurethane based materials. To install PROMASEAL® IBS™, compress and insert into the joints. For gaps up to 30mm, it is possible to install the PROMASEAL® IBS™ in the centre of the depth/thickness of the floor or wall without a sealant fill. The fire reistance achieved depends on the existing fire resistance level of the building element in which the PROMASEAL® IBS™ is installed.

Health & Safety
< #Back#

HEALTH & SAFETY

No special precautions are required. For more information please check the material safety data sheet;

 

WASTE DISPOSAL

Handle as construction industry waste and dispose of in compliance with all local and national regulations in the appropriate and approved manner.

HEALTH & SAFETY

No special precautions are required. For more information please check the material safety data sheet;

 

WASTE DISPOSAL

Handle as construction industry waste and dispose of in compliance with all local and national regulations in the appropriate and approved manner.

Documents
< #Back#

Safety Datasheet (SDS)

Safety Datasheet (SDS)

Product Datasheet

Product Datasheet

System Certificate

System Certificate

Safety Datasheet (SDS)

Safety Datasheet (SDS)

Product Datasheet

Product Datasheet

System Certificate

System Certificate